Food trailer power: 30A vs 50A shore power and generators
How to size the electrical system for a food trailer: what runs on propane, what runs on power, 30A vs 50A shore inlets and choosing a generator.
By the Rolling Retail build team · · 6 min read
Key takeaways
- Put cooking heat on propane; keep electrics for refrigeration, water, lights, fans and the till.
- A 30A/120V inlet supplies about 3.6 kW; a 50A/240V inlet supplies about 12 kW.
- Espresso machines and electric ovens are the loads that push builds to 50A.
- Size generators for start-up surges from compressors, not just running watts.
Power is the system buyers think about last and regret first. Our rule: the power plan must close on paper before anyone renders the trailer.
What runs on what
| Load | Source | Notes |
|---|---|---|
| Griddle, fryer, plancha, deck oven | Propane | Under the extraction hood |
| Refrigeration and freezers | Electric | Runs continuously; surge on start |
| Espresso machine | Electric | Often the largest single load |
| Extraction fan, lights, pumps | Electric | Small but always on |
| HVAC | Electric | Large; needed for walk-in and hot climates |
| POS and menu screens | Electric | Small |
30A or 50A?
A 30A, 120V inlet supplies roughly 3.6 kW — enough for a cold line with modest refrigeration. A 50A, 240V inlet supplies roughly 12 kW and covers most single-hot-line builds with HVAC. We fit a generator inlet alongside the shore inlet so you can trade where the site has no power.
Choosing a generator
- Add the running watts of everything that can run at once.
- Add the largest start-up surge (compressors can briefly draw several times their running load).
- Add 20–25% headroom.
- Choose an inverter generator for quiet operation at events — many organizers set noise limits.
The designer totals your equipment on a power table automatically. Try it with your menu.